TECHNICAL
Power Supply - 95-265 VAC, 50/60 Hz, 10 W (Isolated from voltage sense on HV model)
Service Type - Single Phase, Three-Phase 3- or 4-Wire (Delta or Wye)
Power Output - USB Regulated 5VDC output, 500 mA Max
Primary Voltage and Current Inputs:
Voltage Channels (Std.) – [L1-L3], 80-265 Volts AC Line-to-Neutral, 458V Phase-to-Phase, CAT III
Voltage Channels (HV) – [L1, L2, L3], 80-600 Volts AC Line-to-Neutral, 600V Phase-to-Phase, CAT III
Current Channels – [CT1-CT-4], 333 mVacrms / 666 mVacrms F.S. Software Selectable,
150% over-range on both scales, 1-6,000 Amps F.S. depending on CT
Current Channel Limits – 12 Vdc maximum, current must be limited to 50 mA continuous
Measurement Type – Polyphase Multifunction Energy Metering Digital Signal Processor (DSP)
Line Frequency – 50/60 Hz
Waveform Sampling – 8 kHz
Analog Bandwidth – 2 kHz
Parameter Update Rate – Power Measurements at 1/sec., all others at twice line frequency
Measurements – (Voltage & Current Channels 1-3) Volts, Amps, kW, kWh, kVAR, kVARh, kVA, kVAh, PF
– (Current Channel 4) Amps, kVA, kVAh
Accuracy (Standard) – 1% (<0.5% typical) for V, A, kW, kVAR, kVA, PF
Accuracy (Cert Model) – 0.2% (<0.1% typical) ANSI C12.20-2010 Class 0.2
Resolution – 0.01Amp, 0.01 Volt, 0.01 Watt, 0.01 VAR, 0.01 VA, 0.01 PF
Auxiliary Current Inputs:
Current Channels – [CT5-CT8], 333 mVacrms F.S., 248% over-range, 1-6,000 Amps F.S. depending on CT
Current Channel Limits – 12 Vdc maximum, current must be limited to 50 mA continuous
Line Frequency – 50/60 Hz
Waveform Sampling – 1.3 kHz
Analog Bandwidth – 17.7 kHz
Parameter Update Rate – 1/sec.
Measurements – Amps, kVA, kVAh
Accuracy – 1% typical for Amperage
Accuracy – 2% typical for kVA, kVAh
Minimum required current signal for reading is 1% of full scale
Button Switch - Reset and Diagnostic Function Select
Indicators - 3 LEDs (green): 1 LED to indicate power and status, 1 LED to indicate LAN communication, 1 LED to indicate internet communication
COMMUNICATIONS
Ethernet – 10/100 Mbps
USB – 2.0 Host
Security – SSL3.0, 2048 bit
MECHANICAL
Operating Temperature -40° to 60°C (-40° to 140°F)
Humidity 5% to 95% non-condensing
Enclosure NEMA-3R Epoxy Coated Steel
Weight 4.5kg (10 lb)
Dimensions 22.6cm W, 29.7cm H, 12.4cm D (8.9”W, 11.7” H, 4.9”D)
CERTIFICATIONS – UL, FCC
CONTROL RELAY SPECIFICATION
Number of Channels – 4 (3 on HV models)
Relay Type - Single Pole Single Throw Latching Type (no hold current)
Contact Rating - 30A @ 277 Vac (Refer to Relay Specification Sheet for rating details)
HVAC THERMOSTAT SPECIFICATION
Compatible with most residential and commercial HVAC systems
24VAC w/common wire (required)
Single and two stage conventional heating and cooling systems plus heat pumps with auxiliary heat
Zoned forced air and zoned hot water(2 or 3 wire)
Web page design and maintained by B Rad Design Group
Copyright 1997-2015 all images and text copyrighted by Horizon Energy Systems.
All rights reserved and violators will be prosecuted.
Information in this document is subject to change without notice.
Other products and companies referred to herein are trademarks or registered
trademarks of their respective companies or mark holders.